Design · Conductor properties

The required ampacity before conditions of use is already computed as 22.5 amperes for this roof string. The roof correction factor in the notes is 0.71. The table lists 12 AWG copper at 30 amperes and 10 AWG copper at 40 amperes, both at the insulation temperature the designer is using. Which size meets the corrected ampacity?

Answer choices