  "examSlug": "epa-608",
  "examCode": "EPA 608",
  "examName": "EPA Section 608 Technician Certification",
  "outline": {
    "title": "EPA Section 608 technician certification — Fieldguide draft notes",
    "effective": "Draft study notes for the Fieldguide practice bank. Not a Crosscheck pass and not an EPA exam form. Rules below track 40 CFR 82.156, 40 CFR 82.157, and 40 CFR 84.106 as published for use on 2026-10-30. Confirm the current text before a job or a test.",
    "url": "https://www.epa.gov/section608/section-608-technician-certification-test"
  },
  "domains": [
    { "id": "core", "name": "Core", "weight": 40 },
    { "id": "t1", "name": "Type I — Small Appliances", "weight": 20 },
    { "id": "t2", "name": "Type II — High-Pressure", "weight": 20 },
    { "id": "t3", "name": "Type III — Low-Pressure", "weight": 20 }
  ],
  "topics": [
    {
      "slug": "certification-sections",
      "domainId": "core",
      "outlineRef": "Core — certification types",
      "question": "What are the Section 608 certification types, and how is this different from Section 609?",
      "answer": "Section 608 certification has a Core section plus Type I (small appliances), Type II (high-pressure and very-high-pressure stationary appliances other than small appliances), and Type III (low-pressure appliances). Universal means Core plus all three types. Passing is commonly 70 percent on each section you sit. The card you need follows the equipment you open. Section 609 is a separate certification for motor-vehicle air conditioning. A 609 card does not cover a rooftop unit, a rack, or a chiller, and a Type I card does not cover them either. This Fieldguide set is a draft practice bank. It is not an EPA form and it has not had a Crosscheck pass.",
      "citation": {
        "label": "EPA — Section 608 technician certification test topics",
        "url": "https://www.epa.gov/section608/section-608-technician-certification-test"
      }
    },
    {
      "slug": "venting-prohibition",
      "domainId": "core",
      "outlineRef": "Core — venting",
      "question": "When is releasing refrigerant actually illegal, and what is the de minimis exception?",
      "answer": "Knowing venting of ozone-depleting refrigerants and of most substitute refrigerants, during maintenance, service, repair, or disposal, is prohibited. The narrow de minimis exception is a release that happens while you are making a good-faith effort to recover with certified equipment and that you could not reasonably prevent. Opening a system to atmosphere, cutting out a charged coil, or emptying a cylinder outdoors is not de minimis. Nitrogen used as a holding charge after the refrigerant has been recovered is not a refrigerant release. A few specific substitutes, including some uses of carbon dioxide, nitrogen, water, ammonia, and certain hydrocarbons, sit on an exception list in 40 CFR 82.154. Read that list for the appliance in front of you. Do not treat “it is a new refrigerant” as permission to vent. Civil penalties under the Clean Air Act are assessed per day of violation and the dollar cap is adjusted over time, so memorize the rule rather than an old fine printed in a prep book.",
      "citation": {
        "label": "40 CFR 82.154 — prohibition on venting",
        "url": "https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-82/subpart-F/section-82.154"
      }
    },
    {
      "slug": "recover-recycle-reclaim",
      "domainId": "core",
      "outlineRef": "Core — recovery",
      "question": "What is the difference between recover, recycle, and reclaim?",
      "answer": "Recover means remove refrigerant from an appliance and store it in a cylinder, without a purity promise. Recycle means clean it for reuse, typically on site with oil separation and filter-driers, for equipment of the same owner. Reclaim means reprocess it at a reclamation facility to AHRI 700 specifications. Only reclaimed refrigerant is a specification product that can change owners as reclaimed refrigerant. Mixing two recovered refrigerants in one cylinder usually makes reclaim impractical. A reusable recovery cylinder is gray with a yellow top, is filled to about 80 percent so liquid can expand, and is requalified on the interval stamped on the collar, commonly five years. Do not recover into a disposable cylinder.",
      "citation": {
        "label": "EPA — refrigerant recovery and recycling equipment certification",
        "url": "https://www.epa.gov/section608/refrigerant-recovery-and-recycling-equipment-certification"
      }
    },
    {
      "slug": "evacuation-table",
      "domainId": "core",
      "outlineRef": "Core — evacuation levels",
      "question": "Where are the legal evacuation levels, and how do they differ from a dehydration vacuum?",
      "answer": "The legal levels are in Table 1 of 40 CFR 82.156. Inches of mercury vacuum are measured below atmospheric pressure. As published for this draft, very-high-pressure appliances and high-pressure appliances with a full charge under 200 pounds are 0 inches of mercury vacuum. A high-pressure appliance at 200 pounds or more is 4 inches with pre-1993 recovery equipment and 10 inches with post-1993 equipment. Medium-pressure under 200 pounds is 4 and 10 inches on those same equipment dates. Medium-pressure at 200 pounds or more is 4 and 15 inches. Low-pressure appliances are 25 mm Hg absolute. Small appliances use the percentage rule instead: 80 or 90 percent, or 4 inches of mercury vacuum. A 500-micron vacuum before you charge is a dehydration practice so the system is dry. It is tighter than these legal recovery levels and it does not replace them. Older prep books that require 10 inches for every “other” high-pressure system under 200 pounds are describing an earlier table.",
      "citation": {
        "label": "EPA — required level of evacuation of appliances",
        "url": "https://www.epa.gov/section608/required-level-evacuation-appliances"
      }
    },
    {
      "slug": "small-appliance-definition",
      "domainId": "t1",
      "outlineRef": "Type I — definition",
      "question": "Which products are Type I small appliances?",
      "answer": "A small appliance is manufactured, charged, and hermetically sealed in a factory with five pounds or less of refrigerant. Household refrigerators, window units, PTACs, dehumidifiers, drinking-water coolers, and many vending machines are the usual examples when the charge is at or under five pounds. A split system charged in the field is not Type I, even if the charge is small. A hermetic appliance with seven pounds is not Type I either. Passenger-car air conditioning is Section 609, not Type I. Recovery is still required before you open or scrap a small appliance.",
      "citation": {
        "label": "40 CFR 82.152 — small appliance",
        "url": "https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-82/subpart-F/section-82.152"
      }
    },
    {
      "slug": "type-i-recovery-levels",
      "domainId": "t1",
      "outlineRef": "Type I — recovery levels",
      "question": "How much refrigerant must be recovered from a small appliance?",
      "answer": "With recovery equipment manufactured before November 15, 1993, recover 80 percent of the refrigerant whether or not the compressor works. With equipment manufactured on or after that date, recover 90 percent when the compressor works and 80 percent when it does not. Evacuating the appliance to four inches of mercury vacuum also satisfies the requirement. Use certified equipment the way the manufacturer instructs. If the compressor will not run, system-dependent recovery needs both the high side and the low side, because the stopped compressor can isolate the two sides. A piercing valve is temporary. Seal the process tube after recovery. Do not leave the saddle valve as the permanent port.",
      "citation": {
        "label": "40 CFR 82.156(b) — small appliances",
        "url": "https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-82/subpart-F/section-82.156"
      }
    },
    {
      "slug": "hydrocarbon-cabinets",
      "domainId": "t1",
      "outlineRef": "Type I — hydrocarbon refrigerants",
      "question": "How should a refrigerator labeled R-600a or R-290 be handled?",
      "answer": "R-600a is isobutane and R-290 is propane. Both are higher-flammability (ASHRAE A3) hydrocarbon refrigerants used in small factory charges. Do not braze a system that still holds the charge, and do not pull the gas into a recovery cylinder that holds a halocarbon. The venting prohibition has a specific exception list for some hydrocarbon uses. Read 40 CFR 82.154 for that appliance instead of assuming every new refrigerant may be vented, and instead of assuming every hydrocarbon must be recovered like R-134a. The cabinet label is the warning.",
      "citation": {
        "label": "40 CFR 82.154 — venting exceptions",
        "url": "https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-82/subpart-F/section-82.154"
      }
    },
    {
      "slug": "ods-leak-rates",
      "domainId": "t2",
      "outlineRef": "Type II — ODS leak repair",
      "question": "What leak rates apply to a system with 50 or more pounds of ozone-depleting refrigerant?",
      "answer": "40 CFR 82.157 applies to appliances with a full charge of 50 or more pounds of a class I or class II refrigerant, or a blend that contains one. As of the 2020 revision it does not apply to an appliance that contains only a substitute such as an HFC. The trigger rates are 30 percent for industrial process refrigeration, 20 percent for commercial refrigeration, and 10 percent for comfort cooling and other covered appliances, calculated over 12 months. Comfort cooling includes chillers, splits, and rooftop units that condition occupied space. Commercial refrigeration is retail food and cold storage. Owners repair within 30 days, or 120 days if an industrial process must be shut down, and they document an initial verification test and a follow-up verification test. Records matter. Topping off without the calculation is not compliance.",
      "citation": {
        "label": "EPA — stationary refrigeration leak repair requirements",
        "url": "https://www.epa.gov/section608/stationary-refrigeration-leak-repair-requirements"
      }
    },
    {
      "slug": "aim-act-leak-repair",
      "domainId": "t2",
      "outlineRef": "Type II — HFC leak repair",
      "question": "Do HFC systems have a leak-repair rule in 2026?",
      "answer": "Yes, a separate one. Starting January 1, 2026, 40 CFR 84.106 applies leak repair to certain appliances with 15 or more pounds of refrigerant that contains an HFC or a specified substitute with a GWP above 53. The trigger rates match the familiar split: 30 percent industrial process refrigeration, 20 percent commercial refrigeration, and 10 percent for comfort cooling and other covered appliances. Residential and light-commercial air conditioning and heat pumps are excluded from this section. Repair timing is again 30 days, or 120 days for an industrial-process shutdown, with initial and follow-up verification tests. When you study, keep the two charge thresholds apart: 50 pounds of ozone-depleting refrigerant under 40 CFR 82.157, and 15 pounds of covered HFC refrigerant under 40 CFR 84.106. Quoting one number for every gas is how this draft would become a wrong answer.",
      "citation": {
        "label": "40 CFR 84.106 — leak repair",
        "url": "https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-84/subpart-C/section-84.106"
      }
    },
    {
      "slug": "blend-charging",
      "domainId": "t2",
      "outlineRef": "Type II — blends",
      "question": "Why is R-410A not a drop-in for R-22, and how do you charge a blend with glide?",
      "answer": "R-410A runs at a higher pressure than R-22 and uses polyolester oil, which absorbs moisture. Components, relief devices, and hoses have to be rated for that pressure. R-407C, used in some R-22 retrofits, is a zeotropic blend: its components boil at different temperatures. Charge a glide blend as liquid so the cylinder does not fractionate, and throttle that liquid so the compressor does not take a solid slug. Use the dew-point column for superheat and the bubble-point column for subcooling. A sight glass that is bubbling is a clue, not a charging instrument. Mineral oil from an R-22 system does not circulate with these HFC blends.",
      "citation": {
        "label": "EPA — Section 608 technician certification, substitutes and service practices",
        "url": "https://www.epa.gov/section608/section-608-technician-certification-test"
      }
    },
    {
      "slug": "low-pressure-recovery",
      "domainId": "t3",
      "outlineRef": "Type III — recovery",
      "question": "What must happen before a low-pressure chiller is opened?",
      "answer": "Recover refrigerant to 25 mm Hg absolute with certified recovery equipment. If the pressure rises after you hit that level, liquid is still boiling off or the machine has a leak. Recover again until the vacuum holds. Start with liquid when you can, then vapor. Circulate water so a fast pressure drop does not freeze the tubes. Charge an evacuated chiller as vapor into the evaporator and let the vacuum pull the charge in. Do not dump liquid into the compressor. Warm the crankcase before you drain oil, because R-11 and R-123 dissolve in the oil and will foam out of a cold crankcase.",
      "citation": {
        "label": "40 CFR 82.156 Table 1 — low-pressure appliance",
        "url": "https://www.epa.gov/section608/required-level-evacuation-appliances"
      }
    },
    {
      "slug": "purge-and-rupture-disc",
      "domainId": "t3",
      "outlineRef": "Type III — purge and leak test",
      "question": "What does the purge do, and how hard may you pressurize a low-pressure chiller for a leak check?",
      "answer": "Parts of a low-pressure chiller run below atmospheric pressure, so leaks pull air in. Air collects at the top of the condenser. The purge unit removes those non-condensables. A high-efficiency purge loses less refrigerant while it does that. Frequent purge operation means air is still entering, so find the leak. The shaft seal on an open-drive compressor is a common one. A typical rupture disc is set near 15 psig. Leak checks stay at or below about 10 psig. Raise pressure by circulating warm water. Do not use oxygen or unregulated nitrogen, and do not plug the rupture disc to “get a better test.” Water in the refrigerant usually means a tube leak.",
      "citation": {
        "label": "EPA — Section 608 technician certification, Type III",
        "url": "https://www.epa.gov/section608/section-608-technician-certification-test"
      }
    }
  ]
}