Where are the legal evacuation levels, and how do they differ from a dehydration vacuum?

The legal levels are in Table 1 of 40 CFR 82.156. Inches of mercury vacuum are measured below atmospheric pressure. As published for this draft, very-high-pressure appliances and high-pressure appliances with a full charge under 200 pounds are 0 inches of mercury vacuum. A high-pressure appliance at 200 pounds or more is 4 inches with pre-1993 recovery equipment and 10 inches with post-1993 equipment. Medium-pressure under 200 pounds is 4 and 10 inches on those same equipment dates. Medium-pressure at 200 pounds or more is 4 and 15 inches. Low-pressure appliances are 25 mm Hg absolute. Small appliances use the percentage rule instead: 80 or 90 percent, or 4 inches of mercury vacuum. A 500-micron vacuum before you charge is a dehydration practice so the system is dry. It is tighter than these legal recovery levels and it does not replace them. Older prep books that require 10 inches for every “other” high-pressure system under 200 pounds are describing an earlier table.

EPA — required level of evacuation of appliances