How much refrigerant must be recovered from a small appliance?
With recovery equipment manufactured before November 15, 1993, recover 80 percent of the refrigerant whether or not the compressor works. With equipment manufactured on or after that date, recover 90 percent when the compressor works and 80 percent when it does not. Evacuating the appliance to four inches of mercury vacuum also satisfies the requirement. Use certified equipment the way the manufacturer instructs. If the compressor will not run, system-dependent recovery needs both the high side and the low side, because the stopped compressor can isolate the two sides. A piercing valve is temporary. Seal the process tube after recovery. Do not leave the saddle valve as the permanent port.
40 CFR 82.156(b) — small appliances