Which checks happen before a new string inverter is turned on?

Confirm polarity before the DC disconnect closes, and compare measured Voc with the temperature-corrected expectation. About half the expected Voc means modules are missing from the series string or a section is bypassed. Insulation resistance is measured with the string isolated, not while the inverter is exporting. Torque on clamps is the listed value, read with a tool. These are Field Guide draft drills, not a manufacturer’s commissioning sheet.