EPA 608 · FAQ · Type III — Low-Pressure
What must happen before a low-pressure chiller is opened?
Recover refrigerant to 25 mm Hg absolute with certified recovery equipment. If the pressure rises after you hit that level, liquid is still boiling off or the machine has a leak. Recover again until the vacuum holds. Start with liquid when you can, then vapor. Circulate water so a fast pressure drop does not freeze the tubes. Charge an evacuated chiller as vapor into the evaporator and let the vacuum pull the charge in. Do not dump liquid into the compressor. Warm the crankcase before you drain oil, because R-11 and R-123 dissolve in the oil and will foam out of a cold crankcase.
40 CFR 82.156 Table 1 — low-pressure appliance