Fieldguide

EPA 608 · FAQ · Type III — Low-Pressure

What does the purge do, and how hard may you pressurize a low-pressure chiller for a leak check?

Parts of a low-pressure chiller run below atmospheric pressure, so leaks pull air in. Air collects at the top of the condenser. The purge unit removes those non-condensables. A high-efficiency purge loses less refrigerant while it does that. Frequent purge operation means air is still entering, so find the leak. The shaft seal on an open-drive compressor is a common one. A typical rupture disc is set near 15 psig. Leak checks stay at or below about 10 psig. Raise pressure by circulating warm water. Do not use oxygen or unregulated nitrogen, and do not plug the rupture disc to “get a better test.” Water in the refrigerant usually means a tube leak.