PV Associate · FAQ · Design
What two temperature checks size a series string?
In the cold, string Voc must stay at or under the inverter’s maximum DC input and the code voltage limit (600 V DC on one- and two-family dwellings under the 2023 NEC). In the heat, string Vmp must stay inside the MPPT window. Using STC voltage for both checks misses the cold rise and the hot drop. Field Guide’s design drills walk those two edges with the coefficient printed in the item. Confirm the code edition the authority having jurisdiction enforces.
NEC 2023 690.7 and inverter MPPT limits; NABCEP PVA JTA design domain
Same domain