Do HFC systems have a leak-repair rule in 2026?

Yes, a separate one. Starting January 1, 2026, 40 CFR 84.106 applies leak repair to certain appliances with 15 or more pounds of refrigerant that contains an HFC or a specified substitute with a GWP above 53. The trigger rates match the familiar split: 30 percent industrial process refrigeration, 20 percent commercial refrigeration, and 10 percent for comfort cooling and other covered appliances. Residential and light-commercial air conditioning and heat pumps are excluded from this section. Repair timing is again 30 days, or 120 days for an industrial-process shutdown, with initial and follow-up verification tests. When you study, keep the two charge thresholds apart: 50 pounds of ozone-depleting refrigerant under 40 CFR 82.157, and 15 pounds of covered HFC refrigerant under 40 CFR 84.106. Quoting one number for every gas is how this draft would become a wrong answer.

40 CFR 84.106 — leak repair