EPA 608 · FAQ · Type II — High-Pressure
Why is R-410A not a drop-in for R-22, and how do you charge a blend with glide?
R-410A runs at a higher pressure than R-22 and uses polyolester oil, which absorbs moisture. Components, relief devices, and hoses have to be rated for that pressure. R-407C, used in some R-22 retrofits, is a zeotropic blend: its components boil at different temperatures. Charge a glide blend as liquid so the cylinder does not fractionate, and throttle that liquid so the compressor does not take a solid slug. Use the dew-point column for superheat and the bubble-point column for subcooling. A sight glass that is bubbling is a clue, not a charging instrument. Mineral oil from an R-22 system does not circulate with these HFC blends.
EPA — Section 608 technician certification, substitutes and service practices