What leak rates apply to a system with 50 or more pounds of ozone-depleting refrigerant?
40 CFR 82.157 applies to appliances with a full charge of 50 or more pounds of a class I or class II refrigerant, or a blend that contains one. As of the 2020 revision it does not apply to an appliance that contains only a substitute such as an HFC. The trigger rates are 30 percent for industrial process refrigeration, 20 percent for commercial refrigeration, and 10 percent for comfort cooling and other covered appliances, calculated over 12 months. Comfort cooling includes chillers, splits, and rooftop units that condition occupied space. Commercial refrigeration is retail food and cold storage. Owners repair within 30 days, or 120 days if an industrial process must be shut down, and they document an initial verification test and a follow-up verification test. Records matter. Topping off without the calculation is not compliance.
EPA — stationary refrigeration leak repair requirements